Safety Management Systems For Gas
Introduction
94. As a result of amendments to the Gas Act in 2006, every person operating a gas supply system is required to have in place a safety management system (SMS). Specifically section 46A of the Gas Act requires that every person that owns or operates a gas supply system must implement and maintain a safety management system in accordance with regulations made under section 54 of the Act (i.e. the proposed gas safety regulations).
95. The concept of safety management systems is relatively broad and can cover a variety of aspects from public safety to environmental safety and worker safety. The Gas Act's requirements are specifically with respect to public safety. The SMS provisions require that all practicable steps be taken to ensure the supply system does not present a significant risk of serious harm to the public or significant damage to property. The discussion of the proposed SMS regulations is thus from this position and aspects such as environmental safety, worker safety and damage to assets within the supply system are not included in the regulations because they fall outside the scope provided for in the Act.
96. This does not prevent a company from having a SMS which addresses more than public safety matters. The SMS will need to satisfy the requirements of the proposed regulations but can also include other matters as considered relevant by the company, for example, with respect to worker safety.
Persons Required to Implement and Maintain Safety Management Systems
97. For the purposes of SMS a "gas supply system" is defined at section 46A of the Act as the distribution systems, gas installations, fittings and gas appliances that form part of a system for conveying gas to consumers, as specifically defined in the regulations.
98. Basically this means that any party that owns or operates any part of a gas supply system must implement and maintain a SMS unless the regulations provide otherwise.
99. It is proposed the gas safety regulations provide that gas supply systems do not require a SMS where the following criteria are met:
- the gas distribution system receives its gas from another gas distributor (or wholesaler for LPG); and
- the distribution system supplies less than 100,000 MJ gas per annum to consumers on that system; and
- all infrastructure (pipelines, installations and fittings) within that distribution system have been fitted and maintained by a licensed and registered gasfitter.
100. This definition is intended to cover all assets owned or operated by the main gas distributors (for example, NGC, NovaGas, Powerco, Vector, Wanganui Gas) from when gas enters a distribution network until it passes through the "point of supply" to the consumer. The proposed "bright line" value of 100,000 MJ of gas per annum is sufficient to supply, approximately, 500 average homes during that year.
101. It also addresses the circumstances when gas may pass through more than one "point of supply" before being supplied to the actual consumer, for example, reticulated gas supply to shopping mall complexes, industrial parks, subdivisions, communes, retirement villages and apartments. In this situation the owner or operator, of the mall or apartment, for example, is operating a gas supply system. However, requiring owners or operators of such small scale supply systems to have a SMS would impose significant costs and not necessarily result in any improvement in public or property safety. It may make the operation of such systems unviable.
102. The "bright line" is also intended to allow tanked LPG to be supplied on closed local area networks to consumers without triggering the SMS requirements and associated costs.
103. Essentially, the proposed definition of gas supply system will provide that if you are a small scale distributor and all the assets within your supply system fall within the definition of gasfitting work and the competency of gasfitters then a SMS is not required.
104. Examples of how different gas supply scenarios lead to the requirement to have, or not have, a SMS are provided in Table 1.
Table 1: Gas supply scenarios and SMS requirements
| Gas Supply Scenario |
SMS Required |
Comments |
| Network distributors – includes pipes, installations, fittings and appliances used for the conveyance of gas to the point of supply. |
Yes |
Network distributor is required to develop and maintain the SMS for all assets within their gas supply system up to the point of supply to the consumer. |
|
Privately funded gas supply systems that are:
- supplied with less than 100,000MJ of natural gas per annum by another gas distributor; and
- the system's infrastructure, up to the point of supply to the actual consumer, is covered under the scope of gasfitting; and
- the system is not intended or suitable to be handed over to the network distributor.
|
No |
Because the gas supply system meets the exemption criteria a SMS is not required. |
|
Privately funded gas supply systems that are:
- supplied with less than 100,000MJ of LPG per annum by a LPG wholesaler; and
- the systems infrastructure, up to the point of supply to the actual consumer, is covered under the scope of gasfitting.
|
No |
Because the gas supply system meets the exemption criteria a SMS is not required. |
|
Privately funded gas supply systems that are:
- supplied with less than 100,000MJ of gas per annum by another gas distributor (or wholesaler; but
- the systems infrastructure, up to the point of supply to the actual consumer, is outside the scope of gasfitting.
|
Yes |
A SMS will be required to be established by the owner or operator of the gas supply system because of the special skills required to install and maintain the system infrastructure.
|
|
Privately funded gas supply systems that are:
- Planned to be supplied from a wider gas supply system (i.e. this is basically an extension of the original distribution network); and
- the assets within the gas supply system are intended to be handed over to the distribution network owner upon connection to that network (e.g. a new subdivision).
|
Yes |
When the assets are handed over the Network distributor is required to develop and maintain the SMS for the assets up until the point of supply to the individual consumers. |
|
Privately funded gas supply systems includes, but is not limited to:
- Subdivisions (with both reticulated and tank supplied gas)
- Apartments
- Retirement Villages
- Communes
- Commercial Buildings
- Commercial Parks
|
Questions
1. Is the "bright line" set at an appropriate level?
2. Are the exemption criteria sufficient/workable?
3. Is an application or approval system required for the exemptions?
4. Are gasfitters sufficiently qualified to effectively manage small scale gas supply systems?
Operation of Assets Covered Under and SMS
105. In discussion with industry, issues have been raised regarding assets that are covered by a SMS but are "operated" by a third party. For example, it has been suggested that a gas retailer, to turn on/off the supply of gas to a consumer, would require their own SMS because they would be an operator within the supply system.
106. The term operator in the context of SMS applies to a party that has a legal obligation for the management of the asset(s) in question and is not intended to cover individual actions conducted on those assets.
107. In instances such as a gas retailer turning on/off the supply of gas to a consumer, the retailer does not need to have their own SMS. The retailer would, however, be required to abide by the requirements set by the owner of the gas supply system (and covered by a SMS).
Scope of safety management systems
108. The Act requires the regulations to include some specified elements for public safety and provides scope for the regulations to include other elements, where necessary, to meet the Act's intention.
109. Section 54A requires that the regulations for SMSs must provide for requirements relating to:
- Systematic identification of new and existing hazards.
- Taking all practical steps to eliminate, isolate or minimise those hazards.
- Regular assessment of each hazard identified.
- Documentation of the SMS.
- Audit of the SMS.
110. In addition, the Act provides that the SMS regulations may provide for additional requirements, for example, relating to:
- The design, construction, operation, maintenance, and inspection of the system.
- Security and control of access to the gas supply system.
- Skills, knowledge and experience of persons who do, or assist in doing, work on or in connection with the gas supply system.
- Implementation and management of contingency situations that may affect the system.
- Processes for the on-going improvement of safety in connection with the system.
- Investigation of accidents that involve or affect the system.
- Who may conduct audits.
- How often the audits must be conducted.
- Outcomes and objectives of audits.
111. The discretionary items listed above are not restricted and further requirements may be included.
Background to the Proposed SMS Regulations
112. The SMS provisions outlined in this section are based on a risk management approach and rely on the identification, risk assessment and the adequate control of hazards. SMSs that meet the Act's requirements place an obligation on gas distributors to identify hazards, assess their risks and then take all practicable steps to control each hazard such that the residual risk of serious harm to members of the public or significant damage to property is as low as reasonably practicable.
113. The proposed regulations set the minimum SMS requirements. They will be performance based rather than prescriptive, to enable scope for compliance in, what can be, variable situations.
114. A SMS is intended to provide a systematic process for identifying and managing safety risks. The level of risk for which preventative action is required can vary considerably and the Act requires measures to be taken to prevent any gas supply system to which the Act applies presenting a significant risk of serious harm to members of the public and/or significant property damage.
115. Industry, as a whole, appears to have a number of systems in place to manage aspects of safety. It is the intent of these regulations to formalise critical safety requirements and provide for increased confidence in the identification and assessment of hazards associated with gas and overall public safety in relation to gas distribution in New Zealand.
116. It is intended that only one SMS for public safety and property protection be in place for any particular part of the gas supply system. Multiple SMSs for public safety and property protection are neither desired nor considered to adequately address the public safety requirements because they may lead to conflicting arrangements.
117. The following discussion is presented as a combination of both the regulatory requirements and the essential elements defined in the SMS Standard. This approach as been taken because the two are intrinsically linked and solely setting out the regulatory requirements does not provide a complete picture.
Proposed Safety Management System (SMS) Regulations
118. It is proposed that the regulations will provide that every owner or operator of a gas supply system, as defined in the regulations (see paragraphs 97-107 above), will be required to implement and maintain a SMS in the following manner.
1. Description of the System: it is proposed that the owner or operator of a gas supply system will be required to document and describe their supply system including all the assets within the system that they own or are otherwise in control of. The asset description must list the location, physical description (including state of repair), operation and other detail necessary to determine the associated risks and the development of mechanisms for mitigation.
119. The system description will enable identification of what assets are included in the SMS, allow for identification of the associated hazards and enable the risks presented to the public and property to be assessed.
2. Hazard Identification: it is proposed that the owner or operator of a gas supply system will be required to demonstrate that the following processes have been undertaken:
- systematic identification of all hazards posed by the supply system in relation to public safety and property protection, including hazards arising during commissioning, operation, maintenance, and decommissioning of the supply system;
- identification of the points at which the hazards occur; and
- identification of geographic/environmental factors that may affect the magnitude of the hazards.
120. The identification of hazards presented by particular assets, their locations and associated activities is vital in the prevention of "serious harm" to the public and significant damage to property. This is because it defines the areas where risks present themselves, enables their magnitude to be established and allows for the development of measures to mitigate those risks.
121. A particular asset or operation may pose certain hazards; however, the surrounding conditions can affect the level of risk posed. For example a gas leak in a rural area does not present the same level of risk as the same gas leak in a busy a residential area simply because there is a greater number of people within the area that may be affected.
122. The definition of "hazard" is set in the Act as the presence (or absence) of assets, activities or events that may present a significant risk of serious harm to any member of the public or significant damage to property owned by a person other than the owner or operator of the gas supply system.
123. It is noted that the gas industry considers such hazards as being within the "significant hazard" subset of hazards in general. It is intended that an essential part of the SMS process is for gas supply system owners and operators to separate these "significant hazards" from hazards in general by examining the risk associated with each hazard that is identified. Control, appropriate to the circumstances, must then be applied to the "significant hazards" such that the residual risk of serious harm to members of the public or significant damage to property is as low as reasonably practicable.
3. Hazard Assessment: it is proposed that the owner or operator of a gas supply system will be required to demonstrate that the following has been undertaken:
- systematic assessment of the risks of serious harm to members of the public;
- systematic assessment of the risks of significant damage to property.
124. After the hazards have been identified they will be assessed to determine whether they pose significant risks of serious harm or significant property damage. The definition of "serious harm" is set in the Act and relates to harm caused to members of the public. It is proposed that the definition of "significant property damage" will be along the following lines.
Significant property damage is proposed to be damage that is greater than superficial, being such that the property is either damaged beyond repair or requires substantial repair or reconstruction in order to restore it to, at a minimum, the condition prior to it being damaged.
125. The identification and assessment of hazards will be required to be done to the extent practicable.
Question
Have the requirements for hazard identification and assessment been adequately addressed? If not what areas should be considered?
4. Risk Mitigation:
A) It is proposed that the owner or operator of a gas supply system will be required to demonstrate that they have taken "all practicable steps" to mitigate the associated significant risks to public and property from the identified significant hazards to as low as reasonably practicable. It is noted that the steps required are likely to be different with each case.
B) It is proposed that the owner/operator must demonstrate that systems, processes and documentation are in place to manage the significant risks by either elimination, isolation or minimisation of the hazards to the extent practicable in the circumstances.
126. It is noted that the regulations will require only the significant risks to public safety and property to be addressed. Although the legislation does not require the lesser risks to be addressed in the SMS it may be prudent to do so.
C) To demonstrate that "all practicable steps" have been taken to mitigate the significant risks posed by the gas supply system, It is proposed that the SMS must contain evidence that:
- acceptable processes and procedures have been established and are being maintained;
- monitoring procedures have been established and are being maintained;
- actions that need to be taken in situations where the a processes, procedures or monitoring are not adequate are defined.
D) Evidence of acceptable processes and procedures is proposed to include, but not be limited to:
- establishment of the requirements for persons carrying out work on the system, for example skills, knowledge, competence, supervision requirements and training provisions;
- the setting of standards for the equipment and materials used within the supply system;
- establishment of indicators for reporting on the health, effectiveness and adequacy of the SMS;
- establishment of response plans for remedial actions and emergency situations.
127. It is not proposed to regulate the type of evidence that may be provided for mitigation. The intent of this is to provide flexibility in the options that may be taken to achieve the fundamental safety concepts established in the Act. Referring to industry best practice and standards (New Zealand or international) may meet some of the requirements, however, it is noted that the certification process will ultimately confirm whether the system has adequately identified and assessed the hazards and mitigated the significant risks posed.
Question
Have the steps for mitigation been adequately addressed? If not what areas should be considered?
5. Processes for monitoring the on-going effectiveness of the SMS: it is proposed that the owner or operator of a gas supply system will be required to have in place documentation that sets out procedures for:
- monitoring the effectiveness and health of the SMS, for example, by establishing performance indicators and mechanisms for collection of relevant data;
- identifying and addressing areas of concern, from within their SMS and from industry wide and international experience;
- the investigation of accidents, reporting and utilisation of lessons learned; and
- implementing improvements or updates to the system.
128. It is not proposed that the regulations specify an interval for the regular assessment of the identified hazards and mitigation measures put in place. The assessment process is expected to be somewhat of a continual process. In addition to regular on-going reviews it is expected that assessments will be triggered by certain events, such as accidents involving parts of the supply system.
129. The audit certification process (discussed in detail in paragraphs 145 to 149) will review the effectiveness of the on-going maintenance measures in place for a particular SMS and should identify areas where further attention is required.
6. On-going Maintenance of a SMS: it is proposed that the owner or operator of a gas supply system will be required to regularly update the SMS to incorporate, but not limited to, the following aspects including:
- audit findings; and
- changes to the supply system that may change the nature or scale of hazards; and
- changes to the environment in which the supply system operates; and
- accidents, incidents and other experience from elsewhere in the supply system, from other supply systems, and from anywhere else that might be relevant; and
- the passage of time.
130. It is noted that some hazards for public safety or property may be identified through other processes, for example, hazard identification and risk assessments for worker or environmental safety. Where hazards are identified in these other processes they should be incorporated into the public safety SMS.
Question
Are their further aspects for on-going monitoring and maintenance of an SMS that should be considered?
7. Performance Indicators: it is proposed that at a minimum, the owner or operator of a gas supply system will be required to include the following performance indicators in the processes for monitoring the on-going effectiveness of the SMS:
- Accidents/incidents involving members of the public and damage to property;
- Education programmes undertaken;
- Vandalism incidents;
- Asset entry by the public.
131. Performance indicators are an important aspect in determining the overall effectiveness of a SMS. While it will be up to the individual owner/operator to establish the majority of performance indicators within their SMS, it is proposed that the above key performance indicators (KPIs) be set in the regulations.
132. These KPIs are intended to provide the basis for demonstrating that the principles of public safety and property protection are being addressed in connection with the supply system.
133. It is not proposed that any minimum or maximum numbers be set around the KPIs. This is because they are only intended to serve as a mechanism for identifying that these important aspects are being monitored and/or addressed.
134. Data on accidents and incidents involving public safety and property is considered important because it allows the owner or operator and auditor to identify areas within the SMS that may require further attention.
135. The undertaking of educational programmes and monitoring incidents of vandalism and public entry to assets is considered important because they can provide a measure of the effectiveness of the actions being taken to increase public awareness and reduce exposure to the hazards posed.
136. It will be the owner or operator's responsibility to instigate programmes and collect data against these indicators, which will in turn form a key part of the independent audit process.
Question
Are there any other performance indicators that should be mandated in the regulations?
8. Contingency plans for unexpected supply outages: it is proposed that the owner or operator of a gas supply system will be required to include, in the SMS, processes for:
- identifying supply outage events that may pose significant risks of serious harm to members of the public or significant damage to property; and
- managing those risks (i.e. though elimination, isolation or minimisation of the hazards to the extent practicable in the circumstances (contingency planning).
137. It is noted that some of these elements may be addressed under other legislative requirements, such as that for Civil Defence emergencies. This information should be included in the SMS where the hazards identified pose significant risks to the public and/or property.
138. It is noted that there will be no requirement to duplicate risk assessment and mitigation work that has been carried out under other legislation.
Documentation of the SMS
139. The documentation requirements for a SMS are vital to ensure it has addressed the necessary elements. Without some sort of formalised documentation requirements auditing of the SMS could not occur.
140. Documentation in this context does not necessarily require the production of a single document with all the elements contained therein. The documentation may be spread over a number of documents that are referenced and can be brought together for the purpose of auditing. This approach is recognised in the proposed SMS regulatory requirements 1 to 8 that set out a number of documentation requirements.
141. The documentation forming an SMS is not limited to policies, processes and procedures. It may also include maps, plans, photographs, electronic images and knowledge of staff. It is a repository of criteria to be met and actions required to maintain public safety and protect property.
142. The SMS documentation must contain records of the essential elements as provided under proposed regulatory requirements 1 to 8 and includes:
- an up to date description of the system including assets, infrastructure and processes involved;
- the hazards identified;
- the risk assessment for the identified hazards;
- mitigation measures (both in-place and proposed);
- records of on-going maintenance of the system (i.e. periodic assessments);
- records of incidents involving the system.
143. It is proposed that the regulations will specify that all documentation associated with a SMS must:
- be written clearly and unambiguously;
- have established sign-off procedures;
- be communicated to all relevant staff;
- be regularly reviewed and updated; and
- be kept and maintained to be available to auditors when undertaking an audit.
144. The auditor, through the audit process, will review the documentation for the SMS as to its adequacy for the supply system described. Detail regarding the audit requirements and processes is discussed below.
Audit Certification of the SMS
145. It is proposed that the regulations will require every SMS to be audited by an independent third party at least every three years. The auditor will be required to certify that an adequate SMS is in place. The adequacy of the SMS will be based on it meeting the general safety requirements and SMS requirements set out in the regulations. Evidence from performance indicators, set in the regulations and those defined by the owner or operator of the gas supply system will also be used to determine the adequacy of a SMS.
146. It is proposed the regulations will provide that audits are conducted on a progressive basis over a period not exceeding three years. The core objective of the audit process is to provide an independent assessment of the adequacy of the SMS in preventing significant risk of:
- serious harm occurring to any member of the public; and
- significant damage occurring to property not owned by the owner or operator of the supply system.
147. Due to the specialised nature of the auditing process, it is proposed that the qualification requirements for auditors be managed under the Joint Accreditation System of Australia and New Zealand (JAS-ANZ). JAS-ANZ will determine the skills necessary to perform the required auditing functions and will establish an accreditation scheme for conformity assessment bodies1 (CABs). CABs will be required to conduct the independent audit of SMSs.
148. Upon completion of the audit, the CAB will produce an audit report for the owner or operator of the gas supply system. The audit report may indicate areas where further work is required before an audit certificate will be issued or highlight issues that should be addressed before the next audit or within a specified period.
149. Where the CAB considers that the SMS is satisfactory an audit certificate will be issued along with the audit report. The audit report and audit certificate will become part of the SMS "package". The audit certificate, however, is the document that indicates compliance with the SMS regulations. It is proposed that the audit certificate must be supplied, by the owner/operator, to the regulator as proof of compliance. Any non-compliance will be the responsibility of the owner/operator to remedy.
Implementation and Transition
150. An asset owner will be required to obtain a SMS certificate two years from the promulgation of the regulations. The two year period is intended to provide JAS-ANZ sufficient time to establish the audit process, accredit CABs and for owners or operators of gas supply systems to develop and have their SMSs certified.
Enforcement of SMS Provisions
151. Section 46B of the Gas Act makes it an offence for an owner or operator of a gas supply system not have a SMS when they are required to do so. For non-compliance, a fine of up to $250,000 may be imposed. An owner or operator does not have an SMS if it does not have an audit certificate.
Regulator's Role
152. The regulator's role in SMS will be minimal. The regulator, under the general provisions of sections 6 and 7 of the Act, will retain their existing ability to audit any aspects to do with gas safety and compliance with the Act.
Means of Compliance
153. To provide more clarity for owners or operators of gas supply systems meeting the SMS requirements, Standards New Zealand has developed the Standard, NZS 7901 Electricity and Gas Industries – Safety Management Systems for Public Safety. This Standard has been developed by industry with representation from consumers and the regulator.
154. It is proposed that the SMS Standard (NZS 7901) will be a means of compliance for the SMS requirements set in the regulations; however, they will not be the sole means of compliance. Whether an owner or operator of a gas supply system decides to follow the Standard or an alternative means of compliance the CAB, through the audit process, will ultimately decide whether a SMS meets the obligations and requirements set under the Act.
Back to Top